Customization: | Available |
---|---|
Interface: | RS485 |
Protocol: | Yd/T1363.3-2014 |
Still deciding? Get samples of US$ 69/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AMC16-DETT DC power meter is mainly designed for measurement of electric energy in base stations where require load sharing and have no sub-metering function. It is capable of metering 6 circuits DC power, providing working current for Hall-effect sensor, and achieving zero-drift calibration by computer software. This energy meter is an ideal sub-metering solution that allows three operators to efficiently measure energy usage of base stations, significantly reducing operating cost.
Technical parameter |
Index |
|
input |
DC rated voltage |
1 channel: -48VDC |
DC current |
6 channels hall sensors output is 5V,current ratio can be set according to the actual ratio | |
Commercial power monitoring |
1 channel: 0-5VDC | |
Overload capacity |
Voltage:1.2times continued,2 times continued 1s;Current: 1.2 times continued,10 times continued 1s. | |
Accuracy (superposition hall sensors) | 1%In≤I≤10%In error±2.5%; I>10%In error±2% | |
Measurement resolution | Voltage output accuracy 0.01V; current output accuracy 0.01A;power output accuracy 0.01kw; energy output accuracy 0.01kwh. | |
functions |
Basic function | Monitor device system time, total voltage, output total current, power, energy, each channel voltage, current, power, energy; LED indicator display;485 communication. |
Metering function |
Start current: under rated voltage, when the load current value of the meter doesn't exceed 1% of the max. current, the meter starts.Shunt running current: when there is no current in the current circuit of the meter, and 85%-125%of the rated voltage is applied on the voltage circuit, the calculator shall not have more than one digital change. | |
Alarm function |
DC voltage output low alarm,DC voltage output high alarm,one power down alarm, module voltage loss alarm, metering branch error alarm, internal program error alarm, clock error alarm,memory failure alarm, AC input power failure alarm | |
Timing function | support broadcast timing, could remote timing to the meter through RS485 communication. | |
Communication |
Single channel RS485, baudrate 9600bps, can be set to 1200BPS, 2400bps, 4800bps. Communication protocol: standard or custmized |
Hall sensor powersupply | Power supply output:+12V/100mA, -12V/50mA | ||
Clock accuracy | ≤0.5S/d(23ºC), ≤1S/d(-20ºC-60ºC), | ||
Auxiliary powersupply | Voltage range | -40V~-60VDC | |
Power consumption | Whole device≤2W( no hall power supply output) | ||
Storage |
It has the storage function of historical power data and historicalalarm information, and the memory is 2MB | ||
Insulation resistance | ≥40MΩ | ||
environment | Temperature | Working : -20ºC~+60ºC; storage:-40ºC~+70ºC | |
Humidity | ≤98% no condensation, no corrosive gas place | ||
Altitude |
≤4000m | ||
Protection level |
IP20 | ||
Material flame retardent | Terminal glow wire temperature 960ºC±10ºC ,shell glow wiretemperature 650ºC±15ºC | ||
installation |
Standard 35mm din rail | ||
Lightning protection | Voltage input(differential mode) | Peak value 5kA | |
Auxiliary power supply(differential mode) | Peak value 5kA |