Item |
Performance Parameters |
|||
|
Model Series |
ADL200N-CT | ADL400N-CT | ||
|
Measurement |
Grid |
Single-phase | Three-phase four-wire, three-phase three-wire, single-phase three-wire | |
|
Voltage |
Rated voltage |
230V | 3×220/380V,3×230/400V,3×277/480V | |
|
Input Range |
±20% | |||
|
Overload |
1.2 times rating (continuous) ,2 times the rating for 1 second | |||
|
Power consumption |
<0.2VA | |||
|
Accuracy class |
Error ±0.5% | |||
|
Current |
Input current |
80A, 120A, 200A, 300A | 3×80A, 3×120A, 3×200A, 3×300A | |
|
Overload |
1.2 times rating (continuous) ,2 times the rating for 1 second | |||
|
Power consumption |
<0.2VA | |||
|
Accuracy class |
Error ±0.5% | |||
|
Power |
Active, reactive, apparent power, error ±0.5℅ | |||
|
Grid frequency |
45~65Hz, error ±0.5% | |||
|
Response rate |
≤100ms (voltage, current, power) | |||
| ≤1s (electrical energy) | ||||
|
Metering |
Electric energy |
Active energy :Class B (split current transformer)Reactive energy (Class 2 accuracy) | ||
|
electromagnetic compatibility |
Electrostatic discharge immunity class III | |||
| Electrical fast transient burst immunity class IV | ||||
| Surge (shock) immunity Class IV | ||||
|
Security |
Power frequency withstand voltage |
Between communication and signal input, AC4kV 1min | ||
|
Insulation resistance |
Input and output terminals to casing >100MΩ | |||
|
Communication |
Interface and communication protocol |
RS485 interface and Modbus RTU protocol | ||
|
Communication address range |
Modbus RTU:1~ 247; | |||
|
Baud rate |
Support 1200bps-38400bps | |||
|
Environment |
Operating temperature |
-40ºC~+70ºC | ||
|
Storage temperature |
-40ºC~+70ºC | |||
|
Relative humidity |
≤95℅ (without condensation) | |||
|
Altitude |
≤3000m | |||
Supporting transformer specifications
| Ordering specifications | Current transformer parameters | Number of transformers |
| ADL400N-CT/D10 | 80A/26.6mA | 3 |
| ADL400N-CT/D16 | 120A/40mA | 3 |
| ADL400N-CT/D24 | 200A/66.6mA | 3 |
| ADL400N-CT/D36 | 300A/100mA | 3 |