Customization: | Available |
---|---|
After-sales Service: | 2 Year |
Warranty: | 2 Year |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Item |
Performance Parameters |
|||
Model Series |
ADL200N-CT | ADL400N-CT | ||
Measurement |
Grid |
Single-phase | Three-phase four-wire, three-phase three-wire, single-phase three-wire | |
Voltage |
Rated voltage |
230V | 3×220/380V,3×230/400V,3×277/480V | |
Input Range |
±20% | |||
Overload |
1.2 times rating (continuous) ,2 times the rating for 1 second | |||
Power consumption |
<0.2VA | |||
Accuracy class |
Error ±0.5% | |||
Current |
Input current |
80A, 120A, 200A, 300A | 3×80A, 3×120A, 3×200A, 3×300A | |
Overload |
1.2 times rating (continuous) ,2 times the rating for 1 second | |||
Power consumption |
<0.2VA | |||
Accuracy class |
Error ±0.5% | |||
Power |
Active, reactive, apparent power, error ±0.5℅ | |||
Grid frequency |
45~65Hz, error ±0.5% | |||
Response rate |
≤100ms (voltage, current, power) | |||
≤1s (electrical energy) | ||||
Metering |
Electric energy |
Active energy :Class B (split current transformer)Reactive energy (Class 2 accuracy) | ||
electromagnetic compatibility |
Electrostatic discharge immunity class III | |||
Electrical fast transient burst immunity class IV | ||||
Surge (shock) immunity Class IV | ||||
Security |
Power frequency withstand voltage |
Between communication and signal input, AC4kV 1min | ||
Insulation resistance |
Input and output terminals to casing >100MΩ | |||
Communication |
Interface and communication protocol |
RS485 interface and Modbus RTU protocol | ||
Communication address range |
Modbus RTU:1~ 247; | |||
Baud rate |
Support 1200bps-38400bps | |||
Environment |
Operating temperature |
-40ºC~+70ºC | ||
Storage temperature |
-40ºC~+70ºC | |||
Relative humidity |
≤95℅ (without condensation) | |||
Altitude |
≤3000m |
Supporting transformer specifications
Ordering specifications | Current transformer parameters | Number of transformers |
ADL400N-CT/D10 | 80A/26.6mA | 3 |
ADL400N-CT/D16 | 120A/40mA | 3 |
ADL400N-CT/D24 | 200A/66.6mA | 3 |
ADL400N-CT/D36 | 300A/100mA | 3 |