ADW series rail type multi-loop power meters are mainly used for measuring the full electric parameters of multiple three-phase circuits, up to four three-phase loop current inputs can be connected simultaneously. It can measure voltage and current, power, power factor, phase angle, unbalance, harmonic and other parameters.
| ADW200 | ADW210 | ADW220 |
| RS485 | RS485+LCD | RS485+LORA |
| MK | MTL | AWT100 |
| Digital Input: 12 Channels DI Digital Output: 4 Channels DO |
Temperature: 12 External NTC Temp. Measurement; -20ºC~+100ºC; Accuracy ± 2ºC Residual Current: 4 Channels Residual Current Measurement; 10~3000 mA; Accuracy 1% (Class 1) |
Downlink: RS485; Uplink: WiFi, 4G, 2G, NB, Lora, LoraWAN, Ethernet, GPS, Profibus |
| Auxiliary power | AC/DC 85~265V; Consumption≤10VA; | |
|
Input
|
Frequency | 45~65Hz; |
|
Voltage |
AC 3×220V/380V; Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s; Power consumption: ≤ 0.5VA; |
|
|
Current |
AC 5A,100A,400A,600A;(External opening transformer); Power consumption: ≤ 0.5VA; Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s; |
|
|
Measurement accuracy |
Frequency 0.05Hz, voltage,current Class 0.5; 2-31st harmonic accuracy: ± 1%; Active electric energy level 1, reactive electric energy level 2; |
|
|
Features |
Pulse output | Output mode: optocoupler pulse with open collector; |
| Communication | RS485, Modbus-RTU; Baud rate 1200~38400; | |
| Switching Input | Dry contact input, Built-in power supply; | |
| Switching Output |
Output mode: Relay normally open contact output; contact rating: AC 250V/3A DC 30V/3A; |
|