ADL200 din rail energy meter adopts DIN35mm din rail installation with LCD display,it can measure electric parameters and has energy pulse output, RS485 communication,which has the advantages of small size, high precision, good reliability and convenient installation.
It can be flexibly installed in the distribution box to realize the sub-item electric energy measurement, statistics and analysis of different areas and different loads.
Accuracy kWh:Class 1
Frequency:45~65Hz
Communication:RS485(MODBUS-RTU)
Power Supply:154~264Vac
Pulse output:kWh
Function | Function description | Function provide |
Measurement of kWh | Single-phase active kWh (positive and negative),3 months historical energy data frozen storage | standard |
Measurement of electrical parameters | Voltage, Current, Active power, Reactive power, Apparent power, Power factor and Frequency | standard |
LCD Display | 8 bits section LCD display | standard |
Key programming | 3 keys to set parameters like code, address, baud rate, multi-tariff and communication protocol | standard |
Pulse output | Active energy pulse output | standard |
Multi-tariff | Adapt 4 time zones, 2 time interval lists, 14 time interval by day and 4 tariff rates | optional F |
Communication | Communication interface: RS485, Communication protocol: MODBUS-RTU | standard C |
Q: The power or energy count is inaccurate after the meter is powered on.
A: Switch the meter display to the power (active power P, power factor λ) interface, and check whether the power display is negative or not. And whether the power factor is between 0.9-0.95, and then check whether the incoming and outgoing wires of the current signal wire are connected reversely (that is, the current incoming wire must be the same as the incoming wire end of the instrument) and consistent with the wiring diagram on the instrument.
Q: The instrument cannot communicate with the host computer usually after powering on.
A:1. The voltage value between the communication output A and B of the measuring instrument should be between +(4.4-4.5)V;
2. Check whether the communication wiring method is correctly wired in accordance with the wiring diagram requirements (that is, the communication terminal A/B of the corresponding to communication serial port A/B)