Customization: | Available |
---|---|
Communication: | RS485(Modbus-RTU) |
Opening Size: | 88*88mm |
Still deciding? Get samples of US$ 64.8/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Channel: 4 channel 3 phase or 12 channel 1 phase :
Rated Voltage: AC 3×220V/380V
Accurancy: Voltage and current level 0.5, active energy level 1
RS485(MODBUS-RTU)
Opening size: 88*88mm
The AMC300L AC multi-loop intelligent power collection and monitoring device is mainly used for full electrical parameter measurement of multiple loops and can be connected to up to 6 three-phase loops or 18 single-phase loops with current input at the same time. It can measure voltage and current, power, power factor and other parameters.
Technical Parameter |
Indicators |
|||
Input |
Frequency |
45~65Hz; |
||
Voltage |
Rated value: AC 3×220V/380V; |
|||
Overload: 1.2 times the rated value (continuous); 2 times the rated value/1 second; |
||||
Power consumption: ≤ 0.5VA (per circuit); |
||||
Current |
Rated value: AC 100A; |
|||
Overload: 1.2 times the rated value (continuous); 10 times rated value/1 second; |
||||
Power consumption: ≤ 0.5VA (per circuit); |
||||
Function |
Reserved pulse output |
Output mode: optocoupler pulse with Open collector; |
||
Communication |
Modbus RTU protocol ; Baud 1200~38400 |
|||
Switch-ing |
input |
4 dry contact inputs, 2 active (AC 220V input) |
||
output |
Output method: relay normally open contact output; Contact capacity: AC 250V/3A DC 30V/3A; |
|||
Temperature |
Temperature: -20-100 ºC (accuracy ± 2 ºC) |
|||
Measurement accuracy |
Frequency 0.05Hz, voltage and current level 0.5, active energy level 1 |
|||
Auxiliary power supply |
AC/DC 85 to 265V; power consumption ≤ 10VA; |
|||
Security
|
power-frequency withstand voltage |
>AC 2kV/1min; |
||
insulation resistance |
Input and output terminals to casing>100M Ω; |
|||
Environment |
Working temperature:-20ºC~+60ºC; Storage temperature:-40ºC~+70ºC; Relative humidity:≤ 95% without condensation; Altitude: ≤ 2500m; |
|||
Electromagnetic compatibility |
Surge (impact) immunity test level 4; |
|||
Electrostatic discharge immunity test level 3 |
||||