With the rapid development of data centers, the energy consumption of data centers has become more and more prominent, and the energy management and power supply and distribution design of data centers have become hot issues.
An efficient and reliable data center power distribution system solution is an effective way to improve the Power Usage Effectiveness (PUE) of the data center and reduce the energy consumption of equipment.
The AMC series precision power distribution monitoring solution is a complete solution designed for the power distribution monitoring requirements of the column head cabinet in the Internet Data Center (IDC).
Specification | AMC16Z-D | |||
Distribution System | AC | |||
Measure | Bus voltage, current, active power, reactive power, power factor, active energy, reactive energy; Incoming voltage, current, 2-15th harmonic and total harmonic content; Outgoing line current 2-15th harmonic and total Harmonic content, current and power maximum demand, neutral voltage, neutral current, temperature, leakage current |
|||
Bus Voltage | Rated Input | 220V AC | ||
Measure Range | 40~400V AC | |||
Overload | Instantaneous voltage 2 times/30 sec | |||
Current Loop | Incoming Line | CT | Secondary 5A | |
Range | 0~5A | |||
Outgoing Line | CT | Primary 60A | ||
Range | 0.5~60A | |||
Overload | Continuous current 1.2 times, Instantaneous current 10 times/ 5 sec | |||
Frequency | 45~60Hz | |||
Auxiliary Power | AC85~265V / DC100V~350V | |||
Measure Accuracy | the Voltage and Current of Incoming Line | 0.5 | ||
the Power of Incoming Line | 1 | |||
the Voltage and Current of Outgoing Line | 1 | |||
the Power of Outgoing Line | 2 | |||
Consumption | 5VA | |||
Insulation resistance | 100MΩ | |||
Power frequency withstand voltage | Power/Input Signal between ports AC 2KV/1min 50Hz | |||
Environment | Temperature | Working:-15ºC~+55ºC Storage:-25ºC~+70ºC | ||
Humidity | Relative humidity ≤ 93% | |||
Altitude | ≤2500m | |||
Output 2 channels of Switch Value | 5A 250VAC/5A 30VDC | |||
Input Switch Value | 4-way passive dry contact | |||
Zero sequence current | Secondary 0.5~5A | |||
Leakage Current | 10mA~1A | |||
Neutral ground voltage | 0.2V~20V | |||
Temperature | -10ºC~120ºC | |||
Communication | 2 channels of Modbus-RTU | |||
Installation | DIN35mm Din-rail | |||
Protection level | IP20 | |||
Pollution level | 2 | |||
Electromagnetic Compatibility | Anti-static interference | 3 grade | ||
Immunity to fast transient bursts | 3 grade | |||
Anti-surge interference | 4 grade | |||
Resistant to radiofrequency electromagnetic field radiation | 3 grade |
EMC | LVD |