Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 1 Years |
Still deciding? Get samples of US$ 14/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
AMC series AC multi-function panel meter is a smart meter designed for power monitoring needs of power systems, industrial and mining enterprises, utilities, and intelligent buildings, etc. It integrates measurement of power parameters, such as single-phase or three-phase current, voltage, active power, reactive power, apparent power, frequency, power factor.
High-brightness LED/LCD display interface, parameter setting, and control through buttons, ideal for real-time power monitoring systems. Can directly replace conventional power transmitters and measuring instruments. As an intelligent, digital front-end acquisition component, the instrument has been widely used in various control systems, SCADA systems, and energy management systems.
ACR10R-DxxTE4 three phase din rail energy meter with split-core open ct clamps is suitable for power monitoring of grid-connected PV power station, power demand-side management, and other applications. It is easy to install without removing the primary bus bar and cost-effective. It can measure electrical parameters including current, voltage, active power, reactive power, apparent power, frequency, power factor, and so on.
It supports multi-tariff energy metering, 4 quadrant energy metering, harmonic analysis,s, and energy monitoring. Circuit breaker switches' remote signaling' and 'remote controlling' can be realized with digital input and relay output.
APM series power meters of ACREL are power meters that are designed according to IEC standards and synchronized with international advanced technology. APM series meters have full power measurement, energy statistics, analysis of power quality and network communications, and other functions are mainly used for comprehensive monitoring of the quality of the power supply network.
This series of meters use a modular design, with a rich function of the external DI / DO module, AI / AO module, event recording (SOE) module with T-Flash (TF) card, network communication module, can achieve full power measurement of an electrical circuit and monitoring of switch status, Dual RS485 with Ethernet interface can realize data copying of RS485 master station, eliminating the need for data switching exchange. PROFIBUS-DP interface can realize high-speed data transmission and networking functions.
AMC | ACR | APM |
AMC
Technical Parameter | Value | |
Input | Rated Value | AC voltage:Single phaseAC 100V,400V |
Three phaseAC 100V,400V,660V(UL-L,Only 72/ 96) | ||
AC current:AC1A,5A; | ||
DC voltage:1000V,300V,75mV,10V; | ||
DC current: 0-20mA,4-20mA,5A; | ||
Overload | Voltage: 1.2 times rated value(continuous); 2 times rated value /1 second | |
Current:1.2 times rated value(continuous); 10 times rated value /1 second | ||
Frequency | 45Hz~65Hz | |
Power Consumption | Power consumption of each voltage, the current input circuit is less than 0.5VA | |
Accuracy | Class 0.5 | |
Function | Display | LED or LCD |
Communication | RS485, Modbus-RTU protocol;(1 start bit,8 data bit,1 stop bit,no parity) | |
Baud Rate 2400/4800/9600/19200 bps etc. | ||
Alarm | 1 channel passive relay,contact capacity 3A/30VDC,3A/250VAC, Used for high,low,unbalance alarm etc. | |
Analog | DC4~20mA,( load <500Ω) | |
(note: Shielded wire is specially selected for the above signal input and output) | ||
Switching | Input:4 channel or 2 channel dry contact Input, built-in power supply | |
Output:2 channel switching output,NO relay contact,capacity:3A/30VDC,3A/250VAC | ||
Auxiliary Supply | AC/DC 85-265V | |
Power Consumption | <5VA | |
Insulation resistance | ≥ 100MΩ | |
Power frequency withstand voltage | Between power supply set of terminals and signal input, output set of terminals 2kV/1min (RMS) | |
Between the shell and all sets of terminals(except the set of terminals reference voltage less than 40V) AC 4kV | ||
Environment | Temperature | Operation: -10ºC~+55ºCStorage: -25°C ~+70°C |
Humidity | ≤95%RH, no condensation, without corrosive gas | |
Altitude | ≤ 2500m |
Item | Parameter |
Phase | Single-phase; Three Phase, 3P3L, 3P4L |
Frequency | 45~65Hz |
Input Voltage | Rated voltage: AC 57.7V/100V(100V); 220V/380V(400V) |
Overload: 1.2 times the rated voltage(continuous); 2 times the rated voltage lasting for 1 second. Power consumption: less than 0.2VA |
|
Current | Rated current: 80A, 120A, 200A (customized) |
Overload: 1.2 times the rated current(continuous);10 times the rated current lasting for 1 second. Power consumption: less than 0.2VA |
|
Communication | RS485 interface, Modbus-RTU |
Display | LCD |
Accuracy | Voltage, Current, Active: 0.5 grade; Reactive: 1 grade |
Power supply | AC85~265V or DC100~350V; power consumption ≤10VA |
Insulating resistor | Input, output terminal to housing >100MΩ |
Environment | Working temperature: -10ºC~+55ºC; Storage temperature: -20ºC~+70ºC Relative humidity:5%~95%,non-condensing; Altitude:≤2500m |
Technical Parameter | Value | ||
Signal | Connection | 3 phase 3 wire,3 phase 4 wire | |
Frequency | 45~65Hz | ||
Voltage | Rated value:AC 100V,110V,400V,690V | ||
Overload:1.2 times rated value(continuous); 2 times rated value(1 second) | |||
Power consumption:< 0.5VA(per channel) | |||
Current | Rated value:AC 1A, 5A | ||
Overload:1.2 times rated value(continuous);10 times rated value(1 second) | |||
Power consumption:< 0.5VA(per channel) | |||
Measurement Acuracy |
Voltage,current and power | Class 0.5S(APM800,APM810)Class 0.2S(APM801,APM830) | |
Active power | |||
Reactive power | Class 2(APM800, APM810), Class 0.5(APM801,830) | ||
Harmonic | 1%(2-42nd),2%(43~63rd) | ||
Switch inputs | Passive contact inputs,bult-in power supply | ||
Relay outputs | Contact type: open contact in main part, changeover contact in moduleContact capacity:3A/AC 250V 3A/DC 30V | ||
The pulse output of energy | Output mode: Optocoupler pulse with open collectorPulse constant:4000(5A),8000(1A) imp/kWh | ||
Analog outputs | DC 0~20mA,4-20mA,0~5V,1~5V output, accuracy class 0.5%, load resistance s 500Q | ||
Analog inputs | DC 0~20mA,4~20mA,0~5V,1~-5V input, accuracy class 0.5% | ||
Storage card | Standard capacity:4G, TF card up to 32G capacity | ||
Communication | RS485(Modbus-RTU) | ||
Profibus(Profibus-DP) | |||
Ethernet(Modbus-TCP HTTP, DHCP) | |||
Auxiliary power supply | Operating range: AC/DC 85V~265V or AC/DC 115~415V(P2) | ||
Power consumption: The power consumption of the main part s 15VA | |||
Safety | Insulation resistance | >100MQ | |
Electromagnetic compatibility | IEC 61000 standard (Level 4) | ||
Protection level | IP54(Front) | ||
Environment | Operating temperature: -20 °C ~ +65 °C | ||
Storage temperature: -20°C~+70°C | |||
Relative humidity: ≤95%(no condensation) | |||
Altitude: ≤2500m |