Customization: | Available |
---|---|
Type: | Power |
Structure: | Protection |
Still deciding? Get samples of US$ 777/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Rated Parameter | Power Supply | Power supply: AC/DC220V, or AC/DC110V, or DC48V(Reference the wiring diagram) |
Range: Power supply x (1±20%) | ||
Maximum power consumption:≤10W(DC) | ||
Rated Voltage | Rated Voltage: AC100V | |
Range:1-120V | ||
Accuracy:±0.5% | ||
Power Consumption:≤0.5VA(Single phase) | ||
Overload capacity:1.2 times rated voltage for continuous work;2 times for 10 seconds | ||
Rated Current | Rated current: AC 5A/1A(See the device wiring diagram) | |
Range:0.04In~15In | ||
Power consumption:≤0.5VA(Single phase) | ||
Over capacity:2 times rated current for continuous work;40 times for 1 second | ||
Frequency | Rated frequency:50Hz or 60 Hz | |
Range:45~55Hz | ||
Accuracy:±0.1Hz | ||
Digital Input | Rated Voltage: AC/DC220V, AC/DC110V, DC48V(Similar to the power supply) | |
Voltage Range: Rated voltage x (1±20%) | ||
Power Consumption:≤1W(DC220V)(Single channel) | ||
Digital Output | Mechanical life:≥10000 times | |
Switching capacity:≥1000W, L/R=40ms | ||
On current:continuous≥5A short time(200ms)≥30A | ||
Interrupting capacity:≥30W,L/R=40ms | ||
Normal Working Conditions | Ambient temperature:-10ºC~+55ºC | |
Device storage, transport allows the ambient temperature is -25ºC~+70ºC | ||
Relative humidity:5%~95%(The product does | ||
Altitude:≤4000m |
Function | Current Type | Voltage Type |
AM4-I | AM4-U1 | |
Current collection | 4 | 0 |
Voltage collection | 4 | 4 |
Switch value collection | 12 | 12 |
Relay output | 5 | 5 |
Protection Function | ||
Overcurrent (three stages, inverse time limit) | √ | |
Zero sequence overcurrent (two stages, inverse time limit) | √ | |
Negative sequence overcurrent (two stages, inverse time limit) | √ | |
Reclosing | √ | |
Overload trip/alarm | √ | |
Low-frequency load shedding | √ | |
After accelerating overcurrent | √ | |
Overvoltage trip | √ | |
Low voltage trip | √ | |
FC blocking | √ | |
Control failure alarm | √ | |
Non-electricity trip/alarm | √ | |
Low voltage alarm | √ | √ |
Overvoltage alarm | √ | √ |
Zero sequence overvoltage alarm (self-produced/external) | √ | √ |
PT disconnection alarm | √ | √ |
Self-produced zero-sequence overvoltage alarm | √ | |
Communication protocol | ||
Modbus-RTU | √ | √ |
IEC60870-5-103 | √ | √ |
Auxiliary function | ||
Fault recording | √ |
Q: How to set the CT and PT ratio of the protection device?
A: The protection device can set the CT and PT ratio through the fixed value menu. For example, the current transformer is 75/5 and the voltage transformer is 10/0.1, then the CT ratio is set to 15 and the PT ratio is set to 100.
Q: For AM5, if you want to place single circuit protection and transformer protection, how to distinguish the model?
A: AM5-F is suitable for line protection and transformer protection.No need to distinguish between models when placing orders
Q: When the voltage is a three-phase three-wire system, does the current have to be connected with 2CT?
A: The voltage wiring mode and current wiring mode of the protection device can be set independently, and can be connected freely.
Q: How to confirm whether the anti-trip function is configured?
A: If the circuit breaker is equipped with anti-trip, the device does not must be equipped with anti-trip; if the circuit
breaker does not have anti-trip, you need to configure the AM5-FT anti-trip module. (If DC48V is selected as the
operating power supply, the anti-trip box is not optional, and the circuit breaker must be equipped with anti-trip
function; if you choose AC anti-trip, please note that AC and DC general anti-tripping)
Q: How to purchase suitable protection devices?
A: Before ordering, it is recommended to consult related engineers, select the appropriate protection model,
and then fill in the corresponding selection table, and place the order after confirmation by the engineers.
Specification | AM2SE | AM3SE | AM4 | AM5 | AM5SE | |
Hardware | Protect Current | 3 channels | 3 channels | 3 channels | 3 channels | 3 channels |
Measure Current | × | × | × | 3 channels | 3 channels | |
zero-sequence current | 1 channel | 2 channels | 1 channel | 2 channels | 2 channels | |
Measure Voltage | 3 channels | 3 channels | 4 channels | 4 channels | 4 channels+ backup 2 channels | |
Switch Value Input | 8 channels | 11 channels | 12 channels | 16 channels | 20 channels | |
Switch Value Output | 5 channels | 5 channels | 5 channels | 10 channels | 10 channels | |
RS485 Interface | 1 channels | 1 channel | 1 channel | 2 channels | 2 channels | |
RS232 Interface | × | × | 1 | 1 | 1 | |
USB | × | √ | ||||
CE | × | optional 2 | ||||
GPS time synchronization | × | √ | × | √ | √ | |
4-20mA | × | optional 2 | ||||
Anti-jump | Optional external anti-hop module | built-in | ||||
operation circuit | × | √ | ||||
Protection | Main transformer differential protection | × | × | × | × | √ |
Main transformer backup protection | × | × | × | × | √ | |
Three-stage overcurrent With direction with a voltage blocking |
× | × | × | √ | √ | |
Three-stage overcurrent with directional locking |
× | √ | √ | √ | √ | |
Three-stage overcurrent | √ | √ | √ | √ | √ | |
Zero sequence overcurrent protection | √ | √ | √ | √ | √ | |
Overvoltage protection | √ | √ | √ | √ | √ | |
Low voltage protection | √ | √ | √ | √ | √ | |
Zero sequence overvoltage protection | √ | √ | √ | √ | √ | |
High-power motor differential protection (>2000KW) |
× | × | × | × | √ | |
High Voltage Motor Protection | × | × | × | √ | √ | |
Capacitor Protection | × | × | × | √ | √ | |
Overcurrent after acceleration | √ | √ | √ | √ | √ | |
Low-frequency load shedding | √ | √ | √ | √ | √ | |
Grid-connected reverse power protection | × | × | × | √ | √ | |
PT disconnection alarm | √ | √ | √ | √ | √ | |
Fault alarm | √ | √ | √ | √ | √ | |
FC blocking | √ | √ | √ | √ | √ | |
Incoming line of high voltage single busbar system /Mother-joint prepared self-injection |
× | × | × | √ | √ | |
Low-voltage standby self-switching(400V) | × | × | × | √ | × | |
PT monitoring and parallel functions | × | × | × | × | √ | |
PT monitoring functions | √ | √ | √ | √ | √ | |
Non-electrical protection (temperature, gas, etc.) |
√ | √ | √ | √ | √ | |
Synchronization function | × | × | × | × | √ | |
Fault recorder | √ | √ | √ | √ | √ | |
Electrical parameter measurement | U, I, Fr, P, Q, PF, Ep, Eq, Es |