Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 2 Year |
Still deciding? Get samples of $ !
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
APM810 Panel Multifunction Smart Meter have full power measurement, energy statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of the quality of power supply network.
Our APM series meters are suitable for the measurement and display of grid electricity. Active energy measurement accuracy meets the 0.5S level required by IEC62053-22. The APM series of meters provide many high-performance features required to measure and monitor electrical installations. All models are configured with an RS-485 Modbus communication port, two digital inputs, two digital outputs, and critical condition alarms.
Full Electric Parameters Measurement
3-phase (I, U, kW, kVar, kWh, Hz, cosφ)
Current&Voltage Unbalance
Harmonic (THD & 2~63rd)
Real-time&Max Demand
Extremum of this month&last month
Zero-sequence Current
4-quadrant Energy
DO/DI Switch Function Module ---MD82
2 DO Relay Output
8 DI Digital Input
Save up to 128 pcs DO/DI Data in Main Body
Paired with MLOG to save more DO/DI Records
SD Card Data Storage Module ---MLOG
Expand Number of SOE Storage
Support Storage of SD Cards up to 32GB (standard 4GB)
Extra RS485 Communication Module ---MCM
Interface: RS485 Interface
Protocol: MODBUS-RTU
Support Salve&Master Mode
Ethernet Communication Module ---MCME
Interface: RJ45 Interface
Protocol: MODBUS-TCP/HTTP/DHCP/SMTP
Could Serve as Serial Server
Plus 1 Extra RS485 Interface
PROFIBUS-DP Communication Module ---MCMP
Interface: PROFIBUS-DP Interface
Protocol: PROFIBUS-DP
Plus 1 Extra RS485 Interface
SOE Function (Main Body)
Alarm Record (128 pcs records of 66 kinds&13 categories)
DO/DI Record (128 pcs DO/DI records)
Transient Record (800 pcs transient waveform records)
Max Records pcs above could be expanded by SD Card
Multi-rate/Multi-tariff
4 Time zone
4 Tariff rate (Spike, Peak, Flat, Valley)
2 Time period list
14 Time period by day
Local Configuration
Keypads HMI for Programming
Setting through Adjustment Software
Setting through WEB
Setting through MODBUS communication
Technical Parameter |
Value |
|
Signal |
Connection |
3 phase 3 wire, 3 phase 4 wire |
Frequency |
45~65Hz |
|
Voltage |
Rated value: AC 100V,110V,400V,690V |
|
Overload: 1.2 times rated value(continuous); 2 times rated value(1 second) |
||
Power consumption: < 0.5VA (per channel) |
||
Current |
Rated value: AC 1A, 5A |
|
Overload: 1.2 times rated value(continuous); 10 times rated value(1 second) |
||
Power consumption: < 0.5VA (per channel) |
||
Measurement accuracy |
Voltage,current and power |
Class 0.5S (APM800,APM810) |
Active power |
||
Reactive power |
Class 2(APM800, APM810), Class 0.5(APM801,830) |
|
Harmonic |
1%(2~42nd),2%(43~63rd) |
|
Switch inputs |
Passive contact inputs, built-in power supply |
|
Relay outputs |
Contact type: open contact in main part, changeover contact in module Contact capacity:3A/AC 250V 3A/DC 30V |
|
Pulse output of energy |
Output mode: Optocoupler pulse with open collector Pulse constant:4000(5A),8000(1A) imp/kWh |
|
Analog outputs |
DC 0~20mA,4~20mA,0~5V,1~5V output, accuracy class 0.5%, load resistance ≤ 500Ω |
|
Analog inputs |
DC 0~20mA,4~20mA,0~5V,1~5V input, accuracy class 0.5% |
|
Storage card |
Standard capacity:4G,TF card up to 32G capacity |
|
Communication |
RS485(Modbus-RTU) |
|
Profibus(Profibus-DP) |
||
Ethernet(Modbus-TCP,HTTP,DHCP) |
||
Auxiliary power supply |
Operating range: AC/DC 85V~265V or AC/DC 115~415V(P2) |
|
Power consumption: Power consumption of the main part ≤ 15VA |
||
Safety |
Insulation resistance |
>100MΩ |
Electromagnetic compatibility |
IEC 61000 standard (Level 4) |
|
Protection level |
IP54(Front) |
3-phase 4-wire connection via 3 extra CTs
3-phase 3-wire connection via 2 extra CTs & 2 extra PTs