Customization: | Available |
---|---|
Communication: | RS485 (Modbus-RTU) |
Rated Current: | AC 1A, 5A |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Parameter | Description&Value | |
Input | Rated Voltage | AC Voltage Input: 400V or 660V AC L-L (via direct connetion); 100V AC L-L (via -/100V AC PTs) |
Rated Current | AC Current Input: 5A AC or 1A AC (via -/5A AC or -/1A AC CTs) | |
Overload |
Current&Voltage input overload:1.2 times rated value(continuous); 10 times rated value /1 second |
|
Frequency | 45~65Hz | |
Power Consumption |
The power consumption of each current&voltage input circuit is less than 0.5VA |
|
Measuring Accuracy | Voltage | 0.2% |
Current | 0.2% | |
Active Power | 0.5% | |
Reactive Power | 1.0% | |
kWh | 0.5% | |
kart | 1.0% | |
Frequency | ±0.05Hz | |
Harmonic | ±1% | |
Power Supply | Voltage Range | 85-265V AC/DC; 24V or 48V DC (±20%) |
Power Consumption |
≤10VA |
|
Insulation resistance |
≥ 100MΩ |
|
Power frequency withstands voltage |
Between Power supply//Switching Output// Current Input//voltage Input and Transmitting// Communication //Pulse Output//switching input AC 2 kV 1min; Between Power supply,switching output,Current Input,voltage Input AC 2 kV 1min; Between Transmitting,Communication,Pulse Output,switching input AC 1kV 1 min; |
LCD Display
Features of AMC96L-E4 3 Phase Multifunction Power Meter
1. It has RS485 communication interface, and adopts MODBUS-RTU protocol to meet the needs of communication network management;
2. The 4-20mA analog output can correspond to the measured electrical parameters and meet the interface requirements such as DCS;
3. With switch input and relay output, the function of "remote signal" and "remote control" of circuit breaker switch can be realized.