Acrel AKH-0.66/K series split core type current transformers are mainly used in reconstructing projects of urban and rural power grids. The split core current sensors can be mounted easily without the removal of the primary bus. They also can be operated with electricity, which prevents the normal utilization of electricity. Acrel is a professional split core ct manufacturer.
Acrel AKH-0.66/K SCT current transformers series save manpower, material resources, and financial resources and improve the efficiency of users. These split CT transformers match with relay protection, measuring, and metering equipment.
Type | W | H | D | a | e | Primary Input(A) | Net Weight(kg) |
K-30×20 | 90 | 114 | 40 | 22 | 32 | 20-400 | 0.8-0.9 |
K-60×40 | 114 | 140 | 36 | 42 | 62 | 250-2000 | 1.0-2.0 |
K-80×40 | 122 | 162 | 40 | 42 | 82 | 300-3000 | 1.2-2.4 |
K-80×50 | 114 | 159 | 36 | 52 | 82 | 250-1000 | 1.1-1.4 |
K-80×80 | 144 | 159 | 36 | 82 | 82 | 250-1000 | 1.3-1.5 |
K-120×80 | 144 | 199 | 36 | 82 | 122 | 500-1500 | 1.5-2.3 |
K-120×60 | 164 | 214 | 52 | 62 | 122 | 400-5000 | 1.6-3.0 |
K-100×40 | 144 | 194 | A | 42 | 102 | 1000-5000 | 1.6-3.2 |
K-130×40 | 144 | 224 | 52 | 42 | 132 | 1000-5000 | 1.6-3.6 |
K-140×60 | 164 | 234 | 52 | 62 | 142 | 1000-5000 | 1.7-3.7 |
K-160×80 | 184 | 254 | 52 | 82 | 162 | 1000-5000 | 2.8-3.7 |
K-200×80 | 184 | 294 | 52 | 82 | 202 | 1000-5000 | 3.5-4.5 |
Press the arrow direction firmly to open the two screws and press the lower part
Unscrew and pull out the two screws in the direction of the arrow, see "P2"
Pull the screw and pull out the lower part in the direction of the arrow
After installing on the copper busbar, close the lower part in the direction of the arrow, see "P4"
Press firmly in the direction of the arrow
Press the lower part firmly and press the arrow direction to insert the two screws into the holes and tighten the screw width, see "P6"
Then use MS screws and pressure plate to install and press the steel row according to "P6"