DC Leakage Current Sensor

Type: Electromagnetic
Output Signal Type: Analog Output
Production Process: Integration
Material: Metal
Accuracy Grade: 1.0G
Application: Ad, DSP, PLC, Energy Meter
Samples:
US$ 9.1/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2020

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company
  • Overview
  • Product Description
  • Specification
  • Dimension
  • Wiring
  • Installation Instructions
  • After Sales Service
  • Certifications
  • Company Profile
Overview

Basic Info.

Model NO.
AHLC
IP Rating
IP30
Certification
IEC, RoHS
Customized
Customized
Input
10mA-2A
Output
5V
Auxiliary Power
+15V, -15V
Transport Package
Carton
Specification
AHLC
Trademark
Acrel
Origin
China
HS Code
9030339000
Production Capacity
200000

Product Description

Product Description

In recent years, the country's mandatory regulations on electrical fires in various industries have made the DC power supply system have a lot of room for development. The DC power supply system is widely used in various power plants, communication base stations, circuit breaker control power supplies in the field of fire protection, emergency power supplies, etc., In the DC system, the DC leakage current sensor is an indispensable and important component. It detects the DC leakage current of the equipment and is widely used in DC transmission, power storage detection, DC screens, power supplies, large medical and health equipment, photovoltaics, Wind power generation, communication base stations and other industrial equipment. The DC leakage current sensor is a measurement module that uses the principle of fluxgate to convert the measured DC current into a DC current or voltage signal that is output in proportion to the current.

The leakage current sensor is installed around the positive and negative outgoing lines of the photovoltaic DC circuit. When the device is running, the signal output by each branch sensor is detected in real-time. When the branch insulation is normal, the current flowing through the sensor is equal in magnitude and opposite in direction. The output signal is zero; when the branch is grounded, the leakage current sensor has a differential current flowing, and the output of the sensor is not zero. Therefore, by detecting the output signal of each branch sensor, the grounding branch of the photovoltaic DC system can be judged. This principle has high precision in line selection and is not affected by the distributed capacitance of the line.

Specification

Specification Rated current Power supply Rated output Aperture Precision
AHLC-LTA DC 10mA~2A ±15V 5V φ20mm 1
AHLC-EA DC 10mA~2A ±15V 5V φ40mm 1
AHLC-EB DC 10mA~2A ±15V 5V φ60mm 1

 

Dimension

DC Leakage Current Sensor

Size
Spec.

 
Outline size(mm) Through size(mm) Mounting size(mm) Figure
W H D Φ2 Φ1 M N
AHLC-LTA 68 57 20 50 20 52 52 Fig.1
AHLC-EA 100 108 30 75 40 78 / Fig.2
AHLC-EB 120 112 30 94 60 98 / Fig.3
Notes:
1. When the hall sensor is used, in order to obtain better dynamic characteristics and sensitivity, attention must be paid to the coupling between the primary side coil and the secondary side coil. It is recommended to use a single wire and the wire completely fills the hall sensor module wire hole;
2. When the hall sensor is used, the best measurement accuracy can be obtained under the rated input current value. When the measured current is far lower than the rated current To obtain the best accuracy, multiple turns can be used for the primary side, i.e. IPNP = rated ampere-turns. In addition, the temperature of the primary side feeder shall not exceed 80 ºC;
3. The auxiliary power supply of the Hall current sensor shall not exceed ± 20% of the calibrated value when it works normally;
4. Hall current sensor shall not fall from a high place (≥ 1m) during installation and use;
5. It is unable to adjust the zero point and full degree adjustment potentiometer;
6. Auxiliary power supply needs to be configured by itself;
7. The positive and negative poles of the power supply cannot be reversed

Wiring

DC Leakage Current Sensor
DC Leakage Current Sensor
 

Installation Instructions

DC Leakage Current Sensor

After Sales Service

DC Leakage Current Sensor

Certifications

DC Leakage Current Sensor
DC Leakage Current Sensor

 

Company Profile

DC Leakage Current Sensor

Acrel Co., Ltd.[stock code: 300286.SZ] is a high-tech enterprise that integrates R&D, production, sales, and service, since its establishment, is committed to providing users with energy efficiency management and powerful security system solutions. Acrel Electric has a complete production line from cloud platform software to sensors.
Acrel energy efficiency management system including substation operations and maintenance cloud platform, electricity safety management cloud platform, Environmental equipment power consumption monitoring cloud platform, prepaid management (system) cloud platform, intelligent power distribution monitoring system, power quality management system, building energy consumption management system, industrial energy control platform, leakage power monitor and control system, fire-fighting device power monitoring system, fire-proof door monitoring system, emergency lighting and evacuation indicating system, EV charger management system, data center power&environment monitoring system, smart lighting control system, IT isolation power supply system and related products.
The company attaches great importance to product quality and innovation. By the end of 2018, the company has 5 trademarks, 18 invention patents, 72 utility model patents, 94 appearance patents, and 147 computer software Copyrights, and has participated in the formulation of national or industrial standards.
 

DC Leakage Current SensorDC Leakage Current SensorDC Leakage Current SensorDC Leakage Current Sensor

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2020

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory, Trading Company
Registered Capital
10000000 RMB
Plant Area
>2000 square meters