This is an integrated solution for monitoring multi-circuits and mains by using a single meter. The meter is designed for use in both new build and reconstruction and is used for critical power operations in data centers and energy management in buildings. The ideal solution for data center managers, energy or facility managers, engineers, and operational executives who are responsible for delivering power to critical applications
Parameter | AMC16Z-ZA | AMC16Z-FAK24/48 | AMC16Z-ZD | AMC16Z-FDK24/48 | AMC16Z-KD | |
Phase | AC | DC | AC/DC | |||
Channel | 2 | 24/48 | 2 | 24/48 | 48 | |
Measure | U, I, P, Q, S, F, PF, EP, EQ, | U, I, P, E | / | |||
Neutral ground voltage, Neutral current, Total Harmonic content, 2-63rd Harmonic, Voltage phase sequence | 2-63rd Harmonic | |||||
Bus Voltage | Rated Input | 220V AC | 48V DC, 240V DC, 336V DC | |||
Measure Range | 85-280V AC | ±20% | ||||
Overload | Instantaneous voltage 2 times/sec | |||||
Current Loop | Rated Input | 5A | 50mA | 5V | ||
Overload | Continuous current 1.2 times, Instantaneous current 10 times/second | |||||
Frequency | 45-6Hz | / | ||||
Accuracy | U, I: 0.2 EP: 0.5 EQ: 1 |
U, I: 0.5 E: 1 |
||||
Auxiliary Power | signal power(≤15W) | 12-24V DC | signal power(≤15W) | 12-24V DC | 12-24V DC | |
Insulation resistance | 100MΩ | |||||
Power frequency withstand voltage | Power/Input Signal between ports AC 2KV/1min 50Hz | |||||
Environment | Temperature | Working: -15ºC~55ºC Storage: -25ºC~70ºC | ||||
Humidity | Relative humidity ≤ 93% | |||||
Altitude | ≤ 2500m | |||||
Switch Value Output | 2 channels 3A 250VAC / 3A 30VDC |
/ | 2 channels 3A 250VAC / 3A 30VDC |
/ | / | |
Switch Value Input | 6 dry contacts | 24 / 48 -way wet contact | 6 dry contacts | 24 / 48 -way wet contact | 48 dry contacts | |
Communication | RS485 Modbus-RTU | |||||
Installation | Din-rail or Wall-mounted | |||||
Protection level | IP20 | |||||
Pollution level | 2 | |||||
Safety | Insulation | The insulation resistance between all terminals and the conductive parts of the housing is not less than 100MΩ | ||||
Pressure resistance | Signal input, relay output, rs485 communication/leakage/temperature/humidity/auxiliary power supply/switch input together, AC2KV/1min, leakage current less than 2mA, no breakdown, and flashover | |||||
Electromagnetic Compatibility | Anti-static interference | 4 grade | ||||
Immunity to fast transient bursts | 3 grade | |||||
Anti-surge interference | 4 grade | |||||
Resistant to radiofrequency electromagnetic field radiation | 3 grade |
EMC | LVD |