Customization: | Available |
---|---|
Type: | Electromagnetic |
Output Signal Type: | Analog Output |
Still deciding? Get samples of US$ 21.7/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
BA series conduct the real-time measurement on the alternating current in the power grid according to the electromagnetic induction theory. They utilize the precise constant current technology and the linear temperature compensation technology to isolate and convert the measured current into the DC signal. They adopt the 24V or 12V power supply. They feature a large overload capacity, high accuracy, isolation and safety, and low power consumption. Applications cover the industrial automation sector.
Integrated | Splited |
Specification | Input Current | Output Signal | Inner Size(mm) | Type | Optional Function |
BA20(II)-AI/I | AC 0-200A | DC 4-20mA, DC 0-20mA | 20 | Average value | C: RS485; F: Split type |
BA20(II)-AI/V | AC 0-200A | DC 1-5V, DC 0-5V | 20 | Average value | C: RS485; F: Split type |
BA20(II)-AI/I-T | AC 0-200A | DC 4-20mA, DC 0-20mA | 20 | True effective value | C: RS485; F: Split type |
BA20(II)-AI/V-T | AC 0-200A | DC 1-5V, DC 0-5V | 20 | True effective value | C: RS485; F: Split type |
BA50(II)-AI/I | AC 0-600A | DC 4-20mA, DC 0-20mA | 50 | Average value | C: RS485; F: Split type |
BA50(II)-AI/V | AC 0-600A | DC 1-5V, DC 0-5V | 50 | Average value | C: RS485; F: Split type |
BA50(II)-AI/I-T | AC 0-600A | DC 4-20mA, DC 0-20mA | 50 | True effective value | C: RS485; F: Split type |
BA50(II)-AI/V-T | AC 0-600A | DC 1-5V, DC 0-5V | 50 | True effective value | C: RS485; F: Split type |
BA50L(II)-AI/I | AC 0-1A | DC 4-20mA, DC 0-20mA | 50 | Average value | C: RS485; F: Split type |
Technical parameter | Index | ||
Accuracy class | Class 0.5 | ||
Input | Nominal value | BA20(I)-AI | Current AC 0.5A, 50A,200A, etc.AC 0~(0.5~200)A |
BA50(II-AI | Current AC 60A. 300A, 600A, etc. AC0~(60-600)A | ||
BA50L(I)-AI | Current AC0.1A,1A. etc. AC0~(0.1~1)A | ||
Overload | Continuous 1.2 times, instantaneous current 10 times/1S | ||
Absorbed power | ≤1VA | ||
Frequency response | 25Hz~800Hz, especially suitable for industrial frequency occasions | ||
Output | Nominal value | DC4~20mA, or 0~20mA,0~5V,0~10V (1) etc. | |
Load Resistance | When DC12V power supply, current output is ≤250Ω When DC24V power supply, current output is ≤500Ω When voltage output is≥1KΩ |
||
Communication | RS485 interface/Modbus-RTU (2) | ||
Response time | ≤400ms | ||
Power supply | Voltage | DC12V or 24V | |
Power consumption | ≤1W | ||
Insulation resistance | >100MΩ | ||
Compressive strength | Between input/output and power supply 2.0KV/min,50Hz | ||
Temperature Coefficient | -10ºC~+55ºC, ≤400ppm/ºC | ||
Environment | Temperature | Work: -10ºC~+55ºC Storage: -25ºC~+70ºC | |
Humidity | ≤93%RH, no condensation, no corrosive gas place | ||
Altitude | ≤2000m | ||
Installation method | TS35mm Din-rail, or use screws to fix the cabinet |