APM810 Panel Multifunction Smart Meter have full power measurement, energy statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of the quality of power supply network.
Our APM series meters are suitable for the measurement and display of grid electricity. Active energy measurement accuracy meets the 0.5S level required by IEC62053-22. The APM series of meters provide many high-performance features required to measure and monitor electrical installations. All models are configured with an RS-485 Modbus communication port, two digital inputs, two digital outputs, and critical condition alarms.
Technical Parameter |
Value |
|
Signal |
Connection |
3 phase 3 wire, 3 phase 4 wire |
Frequency |
45~65Hz |
|
Voltage |
Rated value: AC 100V,110V,400V,690V |
|
Overload: 1.2 times rated value(continuous); 2 times rated value(1 second) |
||
Power consumption: < 0.5VA (per channel) |
||
Current |
Rated value: AC 1A, 5A |
|
Overload: 1.2 times rated value(continuous); 10 times rated value(1 second) |
||
Power consumption: < 0.5VA (per channel) |
||
Measurement accuracy |
Voltage,current and power |
Class 0.5S (APM800,APM810) |
Active power |
||
Reactive power |
Class 2(APM800, APM810), Class 0.5(APM801,830) |
|
Harmonic |
1%(2~42nd),2%(43~63rd) |
|
Switch inputs |
Passive contact inputs, built-in power supply |
|
Relay outputs |
Contact type: open contact in main part, changeover contact in module Contact capacity:3A/AC 250V 3A/DC 30V |
|
Pulse output of energy |
Output mode: Optocoupler pulse with open collector Pulse constant:4000(5A),8000(1A) imp/kWh |
|
Analog outputs |
DC 0~20mA,4~20mA,0~5V,1~5V output, accuracy class 0.5%, load resistance ≤ 500Ω |
|
Analog inputs |
DC 0~20mA,4~20mA,0~5V,1~5V input, accuracy class 0.5% |
|
Storage card |
Standard capacity:4G,TF card up to 32G capacity |
|
Communication |
RS485(Modbus-RTU) |
|
Profibus(Profibus-DP) |
||
Ethernet(Modbus-TCP,HTTP,DHCP) |
||
Auxiliary power supply |
Operating range: AC/DC 85V~265V or AC/DC 115~415V(P2) |
|
Power consumption: Power consumption of the main part ≤ 15VA |
||
Safety |
Insulation resistance |
>100MΩ |
Electromagnetic compatibility |
IEC 61000 standard (Level 4) |
|
Protection level |
IP54(Front) |
3-phase 4-wire connection via 3 extra CTs
3-phase 3-wire connection via 2 extra CTs & 2 extra PTs
Mining
Petrochemical
Municipal Project
Transportation
Building
Hotel
Hospital
Electric Safety