Customization: | Available |
---|---|
After-sales Service: | Yes |
Warranty: | 2 Years |
Still deciding? Get samples of US$ 130/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Three-Phase Electric Energy Power Monitor Dual Kwh Economy7 Meter by Wireless
ADW series power Internet of Things meters combines traditional power industry various electrical measurement, metering, non-electricity measurement, protection, and other instruments and equipment with the currently popular Internet of Things technology. It breaks the traditional networking, debugging, and application methods. Allow users to see the comprehensive information of the target site more conveniently and intuitively through relevant platforms.
ADW200 | ADW210 | ADW220 |
RS485 | RS485+LCD | RS485+LORA |
MK | MTL | AWT100 |
Digital Input: 12 Channels DI Digital Output: 4 Channels DO |
Temperature: 12 External NTC Temp. Measurement; -20ºC~+100ºC; Accuracy ± 2ºC Residual Current: 4 Channels Residual Current Measurement; 10~3000 mA; Accuracy 1% (Class 1) |
Downlink: RS485; Uplink: WiFi, 4G, 2G, NB, Lora, LoraWAN, Ethernet, GPS, Profibus |
Function
|
Description
|
|||
Energy
Measurement
|
kWh (positive and negative)
|
|||
kvarh (positive and negative)
|
||||
A, B, C three-phase positive kWh
|
||||
Electric Parameter
|
U, I, P, Q, S, PF, Hz
|
|||
Harmonic
|
2-31st voltage and current harmonic
|
|||
Communication
|
RS485 (MODBUS-RTU); baud rate 1200~38400
|
|||
Key Programming
|
4 keypads to set communication and parameters
|
|||
Display
|
LCD display, 8 digits
|
|||
LED Alarm
|
Over-voltage, over-current, interruption phase
|
|||
Data Log
|
Maximum demanded kWh and the time it happened.
|
|||
SOE
|
up to 200 pcs, record on-off status of DO/DI
|
|||
Pulse Output
|
Active optocoupler pulse output with open collector
|
|||
Multi-rate/Tariff
|
4 time zones & 12 time periods
|
Parameters
|
Description
|
|||
Input
|
Voltage
|
AC 3×220V/380V
|
||
Overload: 1.2 times of rated value (continuous); 2 times of rated value / 1s |
||||
Power consumption:≤ 0.5VA
|
||||
Current
|
AC 5A,100A,400A,600A;(external open-type CT)
|
|||
Overload: 1.2 times of rated value (continuous); 10 times of rated value / 1s |
||||
Power consumption:≤ 0.5VA
|
||||
Frequency
|
45~65Hz
|
|||
Measuring
Accuracy
|
Voltage&Current
|
Class 0.5
|
||
Active Power
|
Class 1
|
|||
Reactive Power
|
Class 2
|
|||
Frequency
|
0.05Hz
|
|||
2~31st harmonic
|
± 1%
|
|||
Auxiliary Power
|
AC/DC 85~265V;consumption≤10VA;
|
|||
EMC
|
Better than grade 3
|
|||
Safety
|
Withstand Voltage
|
>AC 2000V/1min
|
||
Insulation Resistance
|
>100MΩ
|
|||
Environment
|
Working Temperature
|
-20ºC~+60ºC
|
||
Storage Temperature
|
-40ºC~+70ºC
|
|||
Humidity
|
≤95% (No condensation)
|
|||
Altitude
|
≤2500m
|
Specification | Input Current | Output Current | Hole Size (mm) for Conductor |
Accuracy Class |
D10 | 5A | 1.25mA | 10mm | Class 0.5 |
D16 | 100A | 20mA | 16mm | |
D24 | 400A | 100mA | 24mm | |
D36 | 600A | 100mA | 36mm |